VGP Pilot Valves

Kromschroder VGP Pilot Valve
Call Us
For tight shutoff of fuel gases and air on industrial and commercial applications
VGP — no damper for speed control
Designed for continuous on-off cycling
Life expectancy of 2 million cycles
DC system prevents overheating of solenoid coil, and high inrush current
Low maintenance
CE certified models available
Application

VGP solenoid valves are normally closed solenoid-operated valves for on/off control of natural gas, LP, clean biogas and air flow. They are widely used as gas safety shut-off valves for industrial and commercial combustion systems.

Specifications

Operating Limits
Ambient temperature range: -4 - 140 °F (-20 - 60 °C) UL up to l04 °F (40°C)
2.2 psig (150 mbar) or 3 psig (200 mbar).
Maximum static line pressure: 30 psig (2.1 bar) (with valve closed)
Opening time: VG. .N fast opening — less than 0.5 seconds
VGP fast opening — <0.5 s
Closing time: <1s
Operating life: 2 million cycles

Electrical Data

Supply voltage: 120 VAC; +101-15%; 50/60 Hz
Duty cycle: Continuous
Type of enclosure: NEMA 3 (IP 54)
Solenoid coil insulation: Class F
Solenoid coil power factor: cos q = 1

Materials of Construction

VGP solenoid valves have pressure die-cast aluminum bodies with nitrile/viton rubber 0-ring seals and valve disc facings. VGP solenoid valves come with DIN plug connector.

Power Consumption at 120 VAC, VA or watts
A full wave rectifier located in the terminal box converts incoming AC current to DC. Power consumption is the same on start-up and during continuous operation.

Valve Size, VGP 10 15 20 25
Pressure Rating 2.2 psig (150 mbar) 35 35
Pressure Rating 3 psig (200 mbar) 26 26
A full wave rectifier located in the terminal box converts incoming AC current to DC. Power consumption is the same on start-up and during continuous operation.